Load
BROWARD COUNTY • 170 MPH DESIGN WIND SPEED

Hurricane Clip vs Strap:
H2.5 vs H10 Uplift Capacity

A roof-to-wall connector rated at 590 lbs looks adequate on paper. At 170 MPH sustained winds, Broward County trusses can demand over 800 lbs of uplift resistance per connection. The wrong connector choice means the difference between a roof that stays and one that peels away panel by panel.

Calculate Uplift Loads See the Comparison
Inspector Alert:

Broward County framing inspectors verify connector type, nail count, and nail size at every truss bearing. A single missing nail on an H2.5A can reduce capacity by 25%, potentially failing the connection below the calculated demand.

0
Design Wind Speed
0
H2.5A Clip Capacity
0
H10 Strap Capacity
0
Capacity Difference

Animated Connection Load Transfer Diagram

Watch how uplift forces travel through clip vs strap connections. Click "Run Load Test" to simulate increasing wind load and see the failure threshold for each connector type.

Real-Time Load Test Simulation

These meters simulate increasing uplift force on each connector. The H2.5A clip reaches its allowable limit at 590 lbs while the H10 strap continues holding to 1,340 lbs — over twice the capacity from a wrap-around design that engages both sides of the truss member.

Simpson H2.5A Clip

Single-sided attachment, (4) 8d nails into truss, (4) 8d nails into plate

0 lbs
Capacity Reached — 590 lbs

Single-wrap connector engages truss from one face only. Load path transfers through nail shear and clip bending.

Simpson H10 Strap

Double-sided wrap-over, (6) 10d nails each side, (4) 10d into plate

0 lbs
Still Holding — Full Capacity

Wrap-over strap engages both faces of the truss. Direct tension load path through galvanized steel eliminates bending weakness.

Specification Comparison: H2.5A vs H10

Every difference matters when the calculated uplift demand determines which connector passes Broward County framing inspection. These are published Simpson Strong-Tie values for Southern Pine lumber connections.

Specification H2.5A Clip H10 Strap
Connector Type Single-sided clip Double-sided wrap-over strap
Allowable Uplift (lbs) 590 1,340
Allowable Lateral (lbs) 315 500
Fastener — Truss Side (4) 8d x 1.5" nails (6) 10d x 1.5" nails per side
Fastener — Top Plate (4) 8d x 1.5" nails (4) 10d x 1.5" nails
Total Fasteners 8 nails 16 nails
Steel Gauge 18 ga galvanized 18 ga galvanized
Engages Both Truss Faces No Yes
Retrofit Friendly (attic) Yes — single-side access No — requires both sides
Approximate Cost per Unit $0.65 – $0.85 $1.40 – $1.80
Insurance Credit Tier Single-wrap (moderate) Double-wrap (highest)
Load Path Mechanism Nail shear + clip bending Direct tension through strap

Nail Pattern Requirements

Broward County inspectors verify exact nail placement. Each dot below represents a required fastener. Missing a single nail on the H2.5A drops its rated capacity from 590 lbs to approximately 445 lbs — potentially below your calculated uplift demand.

H2.5A — 8 Nails Total

TRUSS
TOP PLATE
Truss nails (4) Plate nails (4)

All nails 8d x 1.5" common. Single-sided installation from one face of truss.

H10 — 16 Nails Total

TRUSS (both sides)
TOP PLATE
Truss nails (12) Plate nails (4)

All nails 10d x 1.5" common. Wrap-over strap nailed on both faces of truss member.

When to Use Clips vs Straps

The decision is not always straightforward. Uplift demand, accessibility, truss spacing, and insurance goals all factor into the selection for Broward County projects.

Is calculated uplift demand above 590 lbs per connection?
YES: Use H10 strap or equivalent double-wrap connector. Required for most Broward 170 MPH new construction at 24" o.c. truss spacing.
NO: H2.5A clip may be adequate. Verify with engineer. Common for interior trusses with small tributary areas or low-slope hip roofs.

Choose H2.5A Clip When:

  • Retrofit from attic — Single-side access is the only option without removing ceiling finishes
  • Low uplift zones — Interior trusses on hip roofs where net uplift after dead load offset stays below 590 lbs
  • Budget-constrained retrofits — When upgrading from toe-nails and any connector improvement is the priority
  • Tight framing — Where adjacent blocking prevents strap installation around the truss

Choose H10 Strap When:

  • New construction — No access limitation; install before sheathing when both truss faces are exposed
  • High uplift zones — Gable ends, roof corners, and eave conditions where calculated demand exceeds 600 lbs
  • Insurance optimization — Double-wrap strap classification earns the highest wind mitigation discount tier
  • 170 MPH at 24" o.c. — Standard Broward County truss spacing at full wind speed almost always demands strap-level capacity

Broward County Inspection Requirements

Framing inspection is the critical checkpoint for roof-to-wall connectors. Unlike Miami-Dade's NOA system, Broward County relies on Florida Building Code product approvals and the contractor's submitted connector schedule. Here is what inspectors verify.

Connector Verification

Inspectors confirm the installed connector matches the approved plans. An H2.5A on the plan cannot be substituted with an H1 in the field — even if both are Simpson products. The evaluation report number (ESR or FER) must match.

Nail Count & Size

Every fastener is counted. For an H2.5A, exactly 8 nails must be visible. For an H10, all 16 must be confirmed. Pneumatic nails are acceptable only if the diameter and length match the evaluation report — standard framing gun nails are often undersized.

Embedment & Spacing

Nails must penetrate minimum 1.5 inches into wood members. Nails too close to lumber edges cause splits that void the connection. Minimum edge distance of 3/8 inch from the member edge is enforced, with inspectors rejecting split truss chords.

Common Rejection Reasons in Broward County

  • Wrong nail size — Using 8d nails in an H10 (requires 10d) is the most frequent rejection. The capacity drop is 30-40%.
  • Missing nails — Pneumatic gun misfires leave nails partially driven or at angles. Each missing nail reduces published capacity proportionally.
  • Split lumber — Nailing too close to the edge of 2x4 top plates causes splits. Inspector requires replacement of the plate section.
  • Wrong connector model — Substituting H1 clips for specified H2.5A. Despite similar appearance, H1 has significantly lower capacity at 450 lbs uplift.
  • Connector not at every truss — Plans call for connectors at 24" o.c., but field shows gaps at 48" o.c. or missing connectors at hip corners.

Installation Requirements by Connector Type

Proper installation is what separates a connector that performs to its rated capacity from one that fails at half the published value. These requirements are specific to wood-frame construction with Southern Pine or equivalent species per Simpson Strong-Tie technical literature.

H2.5A Installation Protocol

The H2.5A clip seats against one face of the truss bottom chord where it bears on the top plate. The clip flanges wrap around the plate and truss but do not cross over the top.

  • Step 1: Position clip tight against truss face with both flanges fully seated — no gap between clip and wood
  • Step 2: Drive (4) 8d x 1.5" nails into truss chord through clip holes — hand-nailing recommended to prevent overdriving
  • Step 3: Drive (4) 8d x 1.5" nails into top plate — maintain 3/8" minimum edge distance from plate edges
  • Step 4: Verify no nails protrude through opposite face and no lumber splitting has occurred

H10 Installation Protocol

The H10 strap wraps continuously over the top of the truss bottom chord, with nailing flanges extending down both faces. This creates a mechanical wrap that loads the steel in direct tension rather than bending.

  • Step 1: Bend strap over truss top, centering it on the member. Both legs must be equal length — lopsided installation reduces capacity
  • Step 2: Drive (6) 10d x 1.5" nails per side into truss chord — stagger nails to avoid splitting along the grain line
  • Step 3: Drive (4) 10d x 1.5" nails into top plate — split evenly between both sides of the plate
  • Step 4: Confirm strap lies flat with no kinks or bends in the transition zone over the truss top

The Continuous Load Path Principle

A hurricane clip or strap is only one link in the chain. Broward County's 170 MPH wind creates uplift forces that must travel from the roof sheathing, through the trusses, down the wall studs, through the bottom plate, and into the foundation. A break at any point causes failure.

The roof-to-wall connection is where most continuous load paths fail in older Broward County homes. Pre-2002 construction often relied on three toe-nails per truss — providing roughly 200-300 lbs of uplift resistance per connection. When ASCE 7-22 calculates 800+ lbs of uplift demand at a corner truss under 170 MPH conditions, those three toe-nails represent less than 40% of the required capacity. This is not a marginal shortfall. It is a structural vulnerability that modern connectors were specifically designed to address.

Above the Connection

Roof sheathing must be nailed per the enhanced nailing schedule (8d ring-shank at 4" o.c. edges, 6" o.c. field for Broward HVHZ). Truss top chords transfer sheathing uplift as axial tension down to the bearing point. The connector must then capture this force and transfer it into the wall plate without allowing the truss to separate from the wall.

Below the Connection

The top plate itself needs adequate attachment to the wall studs below. Simpson?"?-type studs-to-plate connectors or properly nailed plate-to-stud connections complete the path. From there, hold-down straps at braced wall segments carry accumulated uplift forces down to the foundation anchor bolts. Each connection in the chain must be designed for the same demand.

Cost vs Insurance Savings Analysis

For a typical 40-truss Broward County home, upgrading from clips to straps adds approximately $50-75 in material cost but can save $400-700 annually in wind insurance premiums through the higher mitigation credit tier.

H2.5A Clip Economics

Material per truss: $0.75 average

Total for 40 trusses: $30.00

Install time per unit: 2-3 minutes

Insurance tier: Single-wrap clip — moderate discount

Adequate for retrofit projects where attic access limits options. The moderate insurance discount still represents meaningful savings over toe-nail-only homes.

H10 Strap Economics

Material per truss: $1.60 average

Total for 40 trusses: $64.00

Install time per unit: 4-5 minutes

Insurance tier: Double-wrap strap — highest discount

The $34 material cost increase for a full house yields the highest insurance credit tier. Payback period is typically under 30 days from the annual premium savings alone.

Frequently Asked Questions

Answers to the most common questions about hurricane clips vs straps in Broward County's wind zone.

What is the allowable uplift load for a Simpson H2.5A hurricane clip?
The Simpson Strong-Tie H2.5A hurricane clip has an allowable uplift load of 590 lbs when installed with the specified nail pattern of (4) 8d x 1.5-inch nails into the truss and (4) 8d x 1.5-inch nails into the top plate. This is a single-sided connector that attaches from one side of the truss-to-plate connection. In Broward County's 170 MPH wind zone, a single H2.5A may not provide sufficient uplift resistance for standard 2-foot on-center trusses at gable ends or corners, requiring either doubled connectors or an upgrade to a strap-type connector.
How does an H10 hurricane strap differ from an H2.5 clip in uplift capacity?
The Simpson Strong-Tie H10 hurricane strap wraps over the top of the truss and fastens on both sides, providing an allowable uplift load of approximately 1,340 lbs — more than double the H2.5A clip capacity. The H10 uses (6) 10d x 1.5-inch nails on each side (12 total into the truss) plus (4) 10d nails into the top plate, for 16 fasteners total. The wrap-around design creates a direct tension load path through the galvanized steel, eliminating the bending stress that limits clip capacity. This mechanical advantage makes straps the preferred choice for Broward County new construction.
When should I use a hurricane clip vs a strap in Broward County?
Use hurricane straps (like the H10) for new construction where calculated uplift loads exceed 600 lbs per connection — common at 170 MPH design wind speed for most roof shapes with 24-inch truss spacing. Hurricane clips (like the H2.5A) are typically adequate for retrofit applications in attic spaces where access to both sides of the truss is limited, or for interior trusses with lower tributary areas on hip roofs. The Florida Building Code Section 2321.6.1 requires connectors to resist the calculated uplift without relying on toe-nails. Your structural engineer's connector schedule should specify the exact model at each truss location based on the calculated demand at that point.
What nail pattern is required for hurricane clips and straps in Broward County?
Nail patterns must match the manufacturer's evaluation report exactly. For the H2.5A clip: (4) 8d x 1.5-inch nails into the truss chord and (4) 8d x 1.5-inch nails into the top plate, all driven flush. For the H10 strap: (6) 10d x 1.5-inch nails on each side into the truss and (4) 10d nails into the top plate. Missing even one nail can reduce capacity by 15-25%. Broward County inspectors verify nail count, nail size, and embedment depth during the framing inspection phase. Pneumatic nailers are allowed only if the nail diameter matches the specification — many framing gun nails are thinner than hand-drive nails of the same penny size.
Do hurricane clips qualify for wind mitigation insurance discounts?
Yes, but the discount tier depends on the connector type. Florida's OIR-B1-1802 wind mitigation form categorizes connections: toe-nails receive no credit; single-wrap clips (H2.5A) qualify for a moderate discount typically saving 15-25% on wind premium; and double-wrap straps (H10) that wrap over the truss and fasten on both sides qualify for the highest discount tier, often saving 30-45% on wind premium. For a Broward County homeowner paying $3,000-5,000 annually in wind insurance, the difference between clip-tier and strap-tier credits can be $400-700 per year.
Can I retrofit hurricane straps from the attic in an existing home?
Retrofit from the attic is possible but constrained. Single-sided clips like the H2.5A or Simpson RT7A are designed for retrofit because they install from one side. Double-wrap straps like the H10 require access to both faces of the truss, achievable only at gable ends or if ceiling drywall is removed. Some contractors use the Simpson LSTA strap, which can be bent around the truss from attic access but requires careful installation to maintain rated capacity. A building permit is required for retrofit connector installation in Broward County, and the work must pass framing inspection before insulation is replaced over the connectors.

Calculate Your Uplift Demand

Knowing whether your Broward County trusses need clips or straps starts with calculating the actual uplift force at each connection point. Get your MWFRS wind loads in minutes.

Calculate MWFRS Loads Browse All Calculators